SOFAR 7.5KTLM User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
Figure 4-5 Connecting DC input power cables
1.Positive power cable 2.Negative power cable
Note: L2 is 2 to 3 mm longer than L1.
Step 3 Insert the positive and negative power cables into corresponding cable
glands.
Step 4 Insert the stripped positive and negative power cables into the positive
and negative metal terminals respectively and crimp them using a clamping tool.
Ensure that the cables are crimped until they cannot be pulled out by force less than
400 N, as shown in Figure 4-6.
Figure 4-6 Connecting DC input power cables
1.Positive power cable 2.Negative power cable