OPERATION OF THE DEVICE
96 HYD 5K...20KTL-3PH
If the PV generation is less than the
load consumption, it will discharge
the battery to supply power to the
load.
If PV generation plus Battery
discharge power is less than the
load, the inverter will import power
from the grid.
The priority of power supply: PV, Battery, Grid
The priority of power consumption: Loads, Battery, Grid
NOTE
If it is not allowed to export power to the grid, an energy
meter and/or CT needs to be installed, and the "Anti
Reflux Control" function needs to be enabled.
7.3.2 Time-of-Use Mode
With the Time-of-Use mode, the inverter can be set to charge the
battery in defined intervals of time, date or weekday, depending on
the State of Charge of the battery. Up to 4 rules (rule 0, 1, 2 and 3)
can be set. If more than one rule is valid for any given time, the rule
with the lower number is active. Each rule can be enabled or disabled.
In below example, the battery will be charged with 1 kW, if the SOC is
below 70%, between 2 and 4 o'clock at night, from 22
nd
Dec till 21
st
March:
Set Time-of-use Mode