45m in
www.solaxpower.com
MADE IN CHINA
TEL: +86 571 5850 9376
E-mail: info@solaxpower.com
ADD:No .288 Shizhu Road, Tonglu Eco nomic Development Zone, Don gxing District,
Tonglu City, Zhejiang Provi nce, China.
SolaX Power Co.,Ltd.
S/N:
3/N /PE ~ 400 /230 V
3×24.6 A
170 00 W
170 00 VA
3×2 5 A
Nom inal AC voltage
Nom inal AC current
Rated AC power ( @ 230 V, 50 Hz)
Max . apparent AC power
Max . conti nuous AC current
Nom inal AC grid frequency
Adj ustab le displacement factor range
Ope rating ambient temperature range:
Ing ress protection:
Pow er fact or at rated power
Protective class:
Ove r volta ge category:
Gri d monit oring:
50 Hz
0.90 over-excited...
0.90 under-excited
-20 °C...+60°C
IP5 4(Fans),IP65(Other)
1
I
III (MAINS), II (PV)
G59 /2 / UTE-157 12 / EN50 438 / VDE 0126- 1-1
AS4 777 / VDE-AR- N 4105 / RD 1699 / C1 0/11 /
Model:ZDNY-TL 17000
S/N:
100 0 V
640 V
250 -800 V
22 A/ 22 A
25 A/ 25 A
17420 W
3/N /PE
~ 400 /230 V
3×24.6 A
170 00 W
170 00 VA
3×2 5 A
Max . DC volt age
Rated input voltage
MPP v oltag e range
Max . DC current (input A/input B)
Abs olute m ax. total PV array short circuit
cur rent(input A/input B)
Max . DC powe r ( @ cos ᵩ=1)
Nom inal AC voltage
Nom inal AC current
Rated AC power ( @ 230 V, 50 Hz)
Max . apparent AC power
Max . conti nuous AC current
Nom inal AC grid frequency
Adj ustab le disp lacement factor range
Ope rating ambient temperature range:
Ing ress protection:
Pow er fact or at rated power
Protective class:
Ove r volta ge category:
Gri d monit oring:
50 Hz
0.90 over-excited...
0.90 under-excited
-20 °C... +60°C
IP5 4(Fans),IP65(Other)
1
I
III ( MAINS ), II (PV )
G59 /2 / UTE-157 12 / EN50 438 / VDE 0126- 1-1
AS4 777 / VDE-AR- N 4105 / RD 1699 / C1 0/11 /
Model Name
Manufacture Info
Parameter
Series Number
Labels
4 Technical Data
4.1 DC Input
ZDNY-TL
10000
ZDNY-TL
12000
ZDNY-TL
15000
ZDNY-TL
17000
ZDNY-TL
20000
Max. DC input power (W)
Max. DC input Voltage(V)
MPP voltage range(V)
Rated input voltage(V)
Start input voltage(V)
Max. DC input current A
No. of MPP inputs
Strings per MPP input A
Max. DC input current B
Max. short-circuit current A
Max. short-circuit current B
Strings per MPP input B
Min. DC input Voltage(V)
10260
320-800
220
12300
15370
1742020500
1000
1000100010001000
250
250
250
250
250
380-800350-800400-800
480-800
640640640
640
640
220
220
220
220
22
2222
2222
11
1122
2222
30
3030
3030
15
1530
3030
2
22
22
3
3
3
33
1
13
33
4 Technical
4.3 Efficiency,Safety and Protectoion
4.2 AC Output
Rated output power (V)
Max. apparent AC power(VA)
AC voltage range(V)
AC nominal current(A)
Max.output current(A)
Max.short-circuit current(A)
Displacement power factor
Feed-in phases
THD
Rated grid frequency(Hz)
Rated grid frequency range(Hz)
Connection phases
Rated grid voltage(V)
10000
16
12000
15000
1700020000
14.5
17.421.7
24.6
29
20
24
25
29
40
4050
5050
<3%
<3%
<3%<3%
50
5050
5050
Overvoltage catagory
10000
12000
15000
1700020000
<3%
3/N/PE~230/400V
160-280
44-55
0.9overexcited~0.9underexcited
3
3
III(MAINS),II(PV)
ZDNY-TL
10000
Max. Efficiency
Euro Efficiency
MPPT Efficiency
Safety & Protection
Over/under voltage Protection
DC isolation Impedance Protection
Ground Fault Protection
Grid Monitoring
Ground Fault Current monitoring
DC Injection Monitoring
Back feed current monitoring
Residual current detection
Anti-island protection
Over load protection
Over heat protection
98.2%
97.6%
99.9%
98.2%
97.6%
99.9%
98.2%
97.6%
99.9%
98.2%
97.6%
99.9%
98.2%
97.6%
99.9%
ZDNY-TL
10000
ZDNY-TL
12000
ZDNY-TL
15000
ZDNY-TL
17000
ZDNY-TL
20000
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
13
12
4 Technical
ZDNY-TL
17000