EasyManua.ls Logo

Spirax Sarco LC2250 - Page 38

Spirax Sarco LC2250
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM-P402-130 EMM Issue 9
38
10.6 Input technical data
Level voltage
Minimum voltage 0 Vdc or 1 V (with OUTRANGE function selected)
Maximum voltage 6 Vdc (absolute maximum = 7 Vdc)
Input impedance 28 k
Accuracy 5% FSD over operating range
Repeatability 2.5% FSD over operating range
Resolution 14 bit (0.15 mV approx)
Sample time 260 Hz
4-20 mA(s)
Minimum current 0 mA
Maximum current 22 mA
Input impedance 110 Ω
Accuracy 5% FSD over operating range
Repeatability 2.5% FSD over operating range
Resolution 14 bit (1 uA approx)
Sample time 260 Hz
Level 'out of range' alarm - voltage
Minimum alarm level < 0.2 Vdc
Minimum recovery level > 1 Vdc
Maximum alarm level > 6.5 Vdc
Maximum recovery level < 6 Vdc
Level 'out of range' alarm - current
Minimum alarm level < 2.5 mA
Minimum recovery level > 4 mA
Maximum alarm level > 21 mA
Maximum recovery level < 20 mA

Related product manuals