EasyManuals Logo

Spirax Sarco SX80 Installation And Maintenance Instructions

Spirax Sarco SX80
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
IM-P323-35 CH Issue 3
8
SX80/90
8 IM-P323-35: Part No 3231354 Issue 7.0 Feb-13
2.10 Output 3 (OP3) 4-20mA - SX90 only
OP3 is a 4-20mA analogue output in SX90 only.
For functionality see Quick Code Set 2.
Isolated output 300Vac CATII
Configurable 0-20mA or 4-20mA
Max load resistance: 500Ω
Calibration accuracy: < +(1% of reading
+200μA)
2.11 Output 4 (OP4) - SX90 only
Output 4 is a changeover (Form C) relay fitted in SX90 only.
For functionality see Quick Start Code.
Isolated output 300Vac CATII
Contact rating: 2A 264Vac resistive
2.12 Outputs 5 & 6 (OP5/6) - SX90 only
Outputs 5 and 6 are supplied as normally open (Form A)
relays and are to control motor driven valves.
They share a common connection and are, therefore, not
isolated from each other.
For alarm type see Quick Code Set 3.
Isolated output 300Vac CATII
Contact rating: 2A 264Vac resistive - any
terminal limited to 2A
2.13 Transmitter Power Supply- SX90
only
The transmitter power supply provides an 24V supply to
power an external transmitter.
Isolated output 300Vac CATII
Output 24V +10%, 30mA
2.14 Potentiometer Input - SX90 only
The potentiometer input provides feedback of the valve
position
Potentiometer resistance: 100-10kΩ
Excitation voltage: 0.46 to 0.54V
Short circuit detection: <25Ω
Open circuit detection: >2MΩ
Open circuit wiper detection >5MΩ
2.15 Digital Inputs A & B – SX80 only
These are contact closure inputs which may be configured for
functions listed in section 9.1.11.
Switching:
LA 12Vdc at 12mA max
LB 12Vdc at 40mA
Contact open > 1200Ω.
Contact closed < 300Ω
2.16 Digital Inputs B. C & D - SX90 only
These are contact closure inputs which may be configured for
functions listed in section 9.1.11.
Not isolated from the sensor input
LC and LD not isolated from each other
Switching:
LC/LD 12Vdc at 6mA max
LB 12Vdc at 12mA
Contact open > 1200Ω. Contact closed <
300Ω
2.17 Remote Setpoint Input - SX90 only
There are two inputs; 4-20mA and 0-10
Volts which can be fitted in place of digital
communications
It is not necessary to fit an external burden
resistor to the 4-20mA input
If the 4-20mA remote setpoint input is connected and valid
(>3.5mA; < 22mA) it will be used as the main setpoint (if
configured). If it is not valid or not connected the
controller will try to use the Volts input. Volts sensor
break occurs at <-1; >+11V. The two inputs are not
isolated from each other
If neither remote input is valid the controller will fall back
to the internal setpoint, SP1 or SP2 and flash the alarm
beacon. The alarm can also be configured to activate a
relay (see section 12.1.1) or read over digital
communications.
To calibrate the remote setpoint, if required, see section
16.5.4
A local SP trim value is available in access level 3 (see
section 10.1).
Isolated 300Vac CATII.
2.18 Digital Communications - SX90 only
Digital communications uses Modbus protocol. It is
available in SX90 only as EIA422 (EIA485 5-wire).
EIA422 (5-wire)
Isolated 300Vac CATII.
RV
RI
RC
V
I
AA
AB
AC
Rx+
Rx-
Com.
Tx+
Tx-
HB
HC
HD
HE
HF
5A
5B
5C
OP5
OP6
3A
3B
+
-
V
+
-
3C
3D
PH
PW
PL
D
4A
4C
4B
B
LB
LC
C
4A
4C
4B
B
LB
LC
A
LA
LC
SX80/90
8 IM-P323-35: Part No 3231354 Issue 7.0 Feb-13
2.10 Output 3 (OP3) 4-20mA - SX90 only
OP3 is a 4-20mA analogue output in SX90 only.
For functionality see Quick Code Set 2.
Isolated output 300Vac CATII
Configurable 0-20mA or 4-20mA
Max load resistance: 500Ω
Calibration accuracy: < +(1% of reading
+200μA)
2.11 Output 4 (OP4) - SX90 only
Output 4 is a changeover (Form C) relay fitted in SX90 only.
For functionality see Quick Start Code.
Isolated output 300Vac CATII
Contact rating: 2A 264Vac resistive
2.12 Outputs 5 & 6 (OP5/6) - SX90 only
Outputs 5 and 6 are supplied as normally open (Form A)
relays and are to control motor driven valves.
They share a common connection and are, therefore, not
isolated from each other.
For alarm type see Quick Code Set 3.
Isolated output 300Vac CATII
Contact rating: 2A 264Vac resistive - any
terminal limited to 2A
2.13 Transmitter Power Supply- SX90
only
The transmitter power supply provides an 24V supply to
power an external transmitter.
Isolated output 300Vac CATII
Output 24V +10%, 30mA
2.14 Potentiometer Input - SX90 only
The potentiometer input provides feedback of the valve
position
Potentiometer resistance: 100-10kΩ
Excitation voltage: 0.46 to 0.54V
Short circuit detection: <25Ω
Open circuit detection: >2MΩ
Open circuit wiper detection >5MΩ
2.15 Digital Inputs A & B – SX80 only
These are contact closure inputs which may be configured for
functions listed in section 9.1.11.
Switching:
LA 12Vdc at 12mA max
LB 12Vdc at 40mA
Contact open > 1200Ω.
Contact closed < 300Ω
2.16 Digital Inputs B. C & D - SX90 only
These are contact closure inputs which may be configured for
functions listed in section 9.1.11.
Not isolated from the sensor input
LC and LD not isolated from each other
Switching:
LC/LD 12Vdc at 6mA max
LB 12Vdc at 12mA
Contact open > 1200Ω. Contact closed <
300Ω
2.17 Remote Setpoint Input - SX90 only
There are two inputs; 4-20mA and 0-10
Volts which can be fitted in place of digital
communications
It is not necessary to fit an external burden
resistor to the 4-20mA input
If the 4-20mA remote setpoint input is connected and valid
(>3.5mA; < 22mA) it will be used as the main setpoint (if
configured). If it is not valid or not connected the
controller will try to use the Volts input. Volts sensor
break occurs at <-1; >+11V. The two inputs are not
isolated from each other
If neither remote input is valid the controller will fall back
to the internal setpoint, SP1 or SP2 and flash the alarm
beacon. The alarm can also be configured to activate a
relay (see section 12.1.1) or read over digital
communications.
To calibrate the remote setpoint, if required, see section
16.5.4
A local SP trim value is available in access level 3 (see
section 10.1).
Isolated 300Vac CATII.
2.18 Digital Communications - SX90 only
Digital communications uses Modbus protocol. It is
available in SX90 only as EIA422 (EIA485 5-wire).
EIA422 (5-wire)
Isolated 300Vac CATII.
RV
RI
RC
V
I
AA
AB
AC
Rx+
Rx-
Com.
Tx+
Tx-
HB
HC
HD
HE
HF
5A
5B
5C
OP5
OP6
3A
3B
+
-
V
+
-
3C
3D
PH
PW
PL
D
4A
4C
4B
B
LB
LC
C
4A
4C
4B
B
LB
LC
A
LA
LC

Table of Contents

Other manuals for Spirax Sarco SX80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Spirax Sarco SX80 and is the answer not in the manual?

Spirax Sarco SX80 Specifications

General IconGeneral
BrandSpirax Sarco
ModelSX80
CategoryController
LanguageEnglish

Related product manuals