© 2023 Radiodetection Ltd 44
Take the dB reading and keep it for reference. If there is
a single fault on the cable, it will be approximately the
same dB value as the reference reading.
NOTE. To establish how often to take readings on the
cable or pipe, move away from the ground stake and take
further readings until the arrow has difficulty in locking and
the dB reading is low. Measure the distance that the
locator is now away from the ground stake. This is the
distance that you can safely use between taking readings
on the cable or pipe to ensure that you do not miss the
fault.
9.3 How to find a fault
Starting from the transmitter, walk along the cable or pipe
route pushing the A-Frame spikes into the ground with the
green spike pointing away from the transmitter. Where
there are no faults the dB reading will be low and the
direction arrow may flicker forward and back.
NOTE: Flickering arrows may also indicate that you may
be too far away from the fault or ground stake (or both) for
the locator to lock on.
Figure 9.1: Cable sheath fault-finding
If you are trying to locate high resistance faults or there is
a long distance between faults, carry on with the survey
and the locator will lock on when you get closer to the fault.
Figure 9.2: Locating faults with the locator and A-frame
Take readings at the survey intervals determined by the
reference reading. To locate the cable or pipe while using
the fault find signal during a Fault-Find survey, press the
key once and the locator will switch to Peak locate
mode. To use alternative antenna modes, press the
key to step through available antenna modes. To get back
to fault find mode step through all available antenna
modes until the locator goes back to fault find mode.
NOTE: While the A-Frame is connected to the locator,
depth and current measurements will not be available. If
depth or current measurements are required, remove the
A-Frame lead from the locator.
As a fault is approached the Fault-Find direction arrow will
lock on to the fault signal, point forward and the dB
readings will increase. When the fault is passed the arrow
will point back towards the transmitter. Take readings at
smaller survey intervals to determine the exact point of the
fault.
When the A-frame is directly over the fault the dB reading
will drop as shown opposite.
NOTE: The values given are for illustration purposes only
and may not be the same as those obtained in other
situations.
To pinpoint the fault, turn the A-frame 90° to the cable or
pipe and Fault-Find until the exact point is found. Where
the arrow direction changes the center line of the A-frame
is now directly over the fault.
Mark the ground to show the position of the fault. Find the
maximum dB reading in front of the fault by pushing the
A-frame into the ground at small intervals. Note the dB
reading. If the reading is approximately the same as the
reference reading, you can assume that there is only one
fault. If the reading is less than the reference reading,
keep surveying the cable for other faults.
NOTE: If the cable or pipe runs under a road, use the
equipment as normal on the road surface as it can
sometimes detect signals when working on blacktop,
concrete, or paved surfaces. If necessary, try wetting the
road surface. Pouring a very small amount of water
around the bottom of the A-frame spikes before each
Fault-Find will generally ensure a good ground
connection.
NOTE: If the cable or pipe runs under a paved surface,
the fault can often be pinpointed by fault finding in the
grass / soil adjacent to the paving. Reduce the distance
between placing the A-frame spikes in the ground to allow
for the increased distance to the actual fault position.