7.4 Internal wiring
For instance, the following types are suitable for the temperature classes listed below:
Distances, creepage distances and clearances
The creepage distances and clearances between the individual components as well
as between the components and the enclosure walls must be dimensioned sufficiently.
The creepage distances between the components must be tested and observed
according to the specifications of the relevant operating instructions.
At least the required clearance, which is the minimum distance between cover and
connection screw of the build-in components (with the conductor connected) must be
observed for all control panels.
Insulation test voltage
As regards insulation and separation of terminals and conductors observe the following:
Insulation test voltage is calculated from the sum of the rated operational voltages of
intrinsically safe and non-intrinsically safe circuits.
"Intrinsically safe against earth"
In case of "intrinsically safe to earth", there is a minimum insulation voltage value of 500
V (otherwise, double value of the rated operational voltage of intrinsically safe circuits).
"Intrinsically safe against non-intrinsically safe"
In case of "intrinsically safe against non-intrinsically safe" the insulation voltage value is
at least 1500 V (otherwise, doubled sum of the rated operational voltage of
intrinsically-safe circuits plus 1000 V).
DANGER
Explosion hazard due to incorrectly routed and damaged conductors!
Non-compliance results in severe or fatal injuries.
Lay the conductors in such a way that damage
(e.g. due to bending, fraying) during operation is avoided.
Adhere to the required creepage distances and clearances.
For the internal wiring use only conductors suitable for the operating
temperature range!
Type Temperature class Conductor cross-
section
H 05 G-K T5 )0.5 mm
2
, Cu
H 07 V-K T6
H 05 V-K T6
LIY T6
H 07 NSGAFÖU T5
or similar types