6 Error and warning messages, faults
06.2017 25
Put down the overload and reduce the load
Correct the cut-off threshold (during commissioning,
with test load)
Overheating 1 or
thermistor error
Lifting and
lowering
blocked
Let the motor cool down the error state is
acknowledged automatically
Check the wiring of the thermistor
Check the thermistor resistance with the motor cold:
– If the measured resistance is 150...750, the
thermistor input is defective and the device must
be replaced.
– If the resistance is greater or smaller, the ther-
mistor is defective and the motor must be re-
placed.
Existing device: check the load sensor see above
New device: carry out offset calibration
If the error occurs in testing bay mode, then check
the load sensor wiring
Lifting and lowering
actuated at the same
time
Lifting and
lowering
blocked
Error in the wiring.
Check the control cables to the terminals 3, 4 and 5
at the SLE
Lifting and
lowering
blocked
Check the voltage at terminal 6
Restart the device
If the error occurs again after a restart, the device
must be replaced
No power supply
available, device fuse
defective
Check the power supply of the device