EasyManua.ls Logo

Startco SE-105 - GF Trip Time; Indication and Reset; SE-105 Outline and Mounting Details

Startco SE-105
15 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Startco Engineering Ltd. Page 1
SE-105 Ground-Fault Ground-Check Monitor Rev. 9
Pub. SE-105-M, November 24, 2005.
1. GENERAL
The SE-105 is a combination ground-fault and ground-
check monitor for resistance-grounded systems in non-
hazardous applications. The ground-fault circuit is
latching and the ground-check circuit is typically non-
latching. One output contact is provided for contactor
control, or for shunt or undervoltage operation in a
breaker trip circuit.
Ground-fault current is sensed by a CT200-series
window-type current transformer. A trip level of 0.5, 2.0,
or 4.0 A is switch selectable for use with a 5-, 15-, or
25-A grounding resistor. Trip time is adjustable from 0.1
to 2.0 seconds.
The fail-safe ground-check circuit is validated by an
end-of-line termination with a 5.6-volt Zener
characteristic. The Zener characteristic clamps induced
voltage and allows induced current to flow in the ground-
check loop. Consequently, induced-ac-withstand
capability, noise immunity, and open/short detection are
independent of current in the phase conductors.
C
AUTION: The SE-105 is not a lock-out device. Follow
lock-out procedures for maintenance.
2. OPERATION
2.1 S
ETTINGS
2.1.1 GF TRIP TIME
Ground-fault trip time is adjustable from 0.1 to
2.0 seconds. Time-coordinated ground-fault protection
requires this setting to be longer than the trip time of
downstream ground-fault devices.
2.1.2 GF
The ground-fault-circuit trip level is 0.5, 2.0, or 4.0 A
when current is sensed with a CT200-series current
transformer. Since the ground-fault-circuit trip level
should not be greater than 20% of the grounding resistor
let-through current, these levels are appropriate for use
with 5-, 15-, or 25-A grounding resistors. For other
applications, the trip level of the ground-fault circuit is
0.25, 1.0, or 2.0% of the primary rating of the
5-A-secondary current transformer.
2.1.3 M
ODE
In the shunt-trip mode (SH), the output relay energizes
and its contact closes if the ground-check loop becomes
invalid or if a ground-fault trip occurs. The shunt-trip
mode is not fail-safe and is not recommended because:
Shunt-trip devices do not operate if supply voltage
fails.
Shunt-trip ground-check circuits allow open cable
couplers to be energized for a short interval after
supply voltage is applied.
In the undervoltage mode (UV), the output relay is
energized and its contact is closed when the ground-check
loop is valid and the ground-fault circuit is not tripped.
The undervoltage mode is referred to as fail-safe and is
recommended because:
Undervoltage devices release if supply voltage fails.
Undervoltage ground-check circuits do not allow
cable couplers to be energized until the ground-
check loop is verified.
2.2 I
NDICATION AND RESET
The green POWER LED indicates that the internal
power supply is on. The red GROUND-FAULT LED
indicates a ground-fault trip and the green GROUND-
CHECK LED indicates a valid ground-check loop. When
a ground-fault trip occurs, the SE-105 remains latched
until the reset switch is pressed or the supply voltage is
cycled. The ground-check circuit is non-latching and
does not require a reset. Terminals are provided for
remote indication and reset as shown in Fig. 1.
For the latching ground-check option, the GROUND-
CHECK LED is red and it indicates a latched ground-
check trip.
2.3 F
USING
The output contact is protected by fuse F1 (4.0 A, time
delay). The ground-check circuit is protected by fuse F2
(0.5 A, time delay).
3. INSTALLATION
3.1 SE-105
SE-105 outline and mounting details are shown in
Fig. 2. Typical connections are shown in Fig. 1. Connect
supply voltage to L1 and L2. For a 120-Vac supply,
connect supply neutral to L2. For a direct-current supply,
connect supply negative to L2. Connect chassis-bonding
terminal
to ground.
Connect contact terminals A and B as required.
Face-plate LED's are driven in series with remote-
indication LED's. When a remote kit is not used,
terminals CI, +, and GI must be connected for the face-
plate LED’s to operate. These jumpers are installed at the
factory.
Connect terminal GC to the outgoing ground-check
conductor and connect terminal G to ground. To meet
electrical code requirements, do not jumper chassis-
bonding terminal
to terminal G.
Install the upper terminal-block cover to prevent
inadvertent contact with line terminals.