STATUS SCIENTIFIC CONTROLS
MCU System Installation and Hardware Configuration Manual
1.6.1 Calculation Examples
Three examples follow demonstrating how the backup time may be calculated.
Example 1 (Typical Configuration)
A 4 channel system comprising of 3 toxic channels and 1 flammable channel. All system relays
are configured as normally energised. No analogue outputs are being provided by the system.
Module and Detector Heads
Input Module & Toxic Head
Input Module & Oxygen Head
Input Module & Flammable Head
Common Relays (Energised)
Input Module Relays (Energised)
Input Module Analogue Output
Total Current Required under normal conditions =
Batteries are 1.2Ahr, therefore backup time is 1200/373 = 3.2 Hrs = 3 Hours 12 mins
Example 2 (Worst Case)
An eight channel system comprising of 8 flammable channels. All system relays are configured as
normally energised. All analogue outputs are providing signals to external equipment.
Module and Detector Heads
Input Module & Toxic Head
Input Module & Oxygen Head
Common Relays (Energised)
Input Module Relays (Energised)
Input Module Analogue Output
Total Current Required under normal conditions =
Batteries are 1.2Ahr, therefore backup time is 1200/856 = 1.4 Hrs = 1 Hour 24 mins