4.1.1 Status Scientific Controls Gas Detectors
Status Scientific Controls design and manufacture a variety of fixed gas detectors. The detector
head used for monitoring oxygen or toxic gases (using conventional sensors) requires a 2-wire
connection whilst detector heads incorporating infrared sensors or pellistors require a 3-wire
connection.
4.1.1.1 FGD2 and FGD3 O
2
and Toxic Detector Heads
Connection Procedure
• Disconnect power from the system.
• Remove the grey protective cover from the associated input module.
• Configure the jumper switches as shown below (i.e. J6, J7, J11, J13 and J14 switched
ON, all others OFF)
• Connect the wires from the detector head to PL1 on the input module observing the
following:
• Connect power to the system and ensure the detector head operates (text on LCD
display, LED will flash once every six seconds approximately).
• Refit grey protective cover.
• Perform software configuration (refer to ‘MCU Software Configuration and System
Calibration Manual’).
• Perform system calibration (refer to ‘MCU Software Configuration and System Calibration
Manual’).