STATUS SCIENTIFIC CONTROLS
MCU System Installation and Hardware Configuration Manual
9 SPECIFICATIONS
9.1 MCU3 & 4 Control Units
Note:
MCU1 and MCU2 now obsolete.
0 to 95% R.H. Non-condensing
24V DC, or 120/230V AC 50/60 Hz Tolerance 10%
Note:
For compliance with UL3101-1 and CSA22.2 No 1010.1, the following environmental conditions apply:
Indoor use; Altitude up to 2000m.
Temperature 0 to 40C.
Maximum relative Humidity 80% decreasing linearly to 50% relative humidity at 40C.
Installation Category (Over Voltage Category) II.
Pollution Degree 2.
Backlit 240 x 64 dot Liquid Crystal Display (LCD)
8 button multifunction keypad
Indicates alarm condition.
Indicates power ON (flashes when powered from int. batteries)
Indicates fault condition.
4-20mA Current Loop from 24V source.
4-20mA Current Loop sink to 0V.
3-Wire Pellistor Systems.
DC Voltage Input.
4-20mA Current source proportional to detected signal.
4-20mA Current sink proportional to detected signal.
1-5V Voltage output proportional to detected signal.
3 – Relays
Contacts
Rating
1 relay assigned to each alarm level (low, medium and high).
Double Pole Changeover Contacts (voltage free).
5A 240V AC.
For specification of common outputs, refer to section 1.3
Connection for normally open switch contacts (5V max present at terminals).
1 Relay assigned to each alarm level (low, medium, high).
1 Relay designated as fault relay.
Double Pole Changeover Contacts (voltage free).
5A 240V AC.