TD06/001
Issue:
6
Change Note:
1696
Page 4-5
4.1.1.4 FGD10B Infrared Current Source
PL1
Terminals
24V
0V
21
22
23
24
Current
sense
circuit
Variable
voltage
output
4-20mA
Out
0V Sup
FGD10B
Connection Procedure
Disconnect power from the system.
Remove the grey protective cover from the associated input module
Configure the jumper switches as shown below (i.e. J6, J7, J10, J12, J13 and J14
switched ON, all others OFF)
J12
J11
J10
J9
J8
J7
J6
J14
J13
Connect a voltmeter (range 0-24V min) between pins 22 (+V) and 24 (0V) of PL1.
Connect power to the system.
Adjust VR1 and VR2 until voltmeter reads between 15V and 24V (VR1 and VR2 provide
fine and coarse voltage adjustment respectively).
Disconnect power to the system and connect the wires from the detector head to PL1 on
the input module observing the following:
Detector Head
PL1
Pin Number
0
24
Supp
22
4-20mA out
21
Connect power to the system and ensure the detector head operates.
Verify that the voltage between the Supp and 0 terminals at the detector head is correct.
Refit grey protective cover.
Perform software configuration (refer to ‘MCU Software Configuration and System
Calibration Manual’).
Perform system calibration.