www.stenner.comEcon FP
auxiliaRy 20%
auxiliaRy 20%
Keypad locKed
+
+
+
+
PROGRAM PUMP SETTINGS
AUXILIARY (12-24VAC/VDC signal) continued
3. Calculate the Pump Speed Percentage.
Metering Pump Output Requirement (gpd) x 100
= Pump Speed Percentage
Metering Pump Maximum Output (gpd)
4. Program the Pump Operating Mode and the Pump Speed Percentage.
Unlock the Keypad
Press and simultaneously and hold for 5 seconds to unlock the keypad.
Pump Operating Mode
First, press and continue to hold , then press or to scroll through the
modes of operation. When the display shows AUXILIARY, release both buttons to select.
The operating mode is now set.
Pump Speed Percentage
The pump speed can be programmed from 10% to 100% in 1% increments. First, press
and continue to hold , then press or to adjust the speed percentage
determined in #3. When the display shows the desired percent, release both buttons to
select. The percentage is now set.
MODE
Example of control panel with the pump speed set for 20%.
MODE
%
%