EasyManua.ls Logo

STIEBEL ELTRON HPG-I 04 S Premium - Internal Heat Source Pump; Temperature Sensor; Pressure Sensors; Pressure Socket Connection Pressure Monitoring

STIEBEL ELTRON HPG-I 04 S Premium
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Repair instructions
HPG-I 04-06-08-12-15 S-CS-DS-DCS
Premium
TQR
Page 41 from 48
D0000095883-c
If no voltage can be measured, the voltage signal at the connector of the MFG board (X70 1-3) and the
wiring must be checked. A bent PIN in the plug socket (PWM input) of the pump may be the cause.
16.2
Internal heat source pump
The volume flow is automatically controlled by the heat pump manager. Manual adjustment of the heat
source pump is not possible.
The internal pump has a positive interference behaviour; without a PWM control signal, it operates at
maximum speed (100%). If the voltage signal is measurable when the PWM pump plug is removed and
collapses when it is plugged in, there is probably a fault in the pump electronics.
If no voltage can be measured, the voltage signal at the connector of the MFG board (X71 1-3) must be
and the wiring must be checked. A bent PIN in the socket (PWM input) of the pump may be the cause.
16.3
Temperature sensor
The connected temperature sensors are PT1000 sensors; an interruption is indicated in the display of the
control unit is displayed with "---".
A test is carried out by measuring the resistance value at the currently prevailing temperature, the
connecting cables, plug-in and clamp connections are to be included.
Sensor temperature
(temperature in °C)
Sensor type PT 1000
(resistance in Ω)
-20
922
-10
961
0
1000
10
1039
20
1078
30
1117
40
1155
50
1194
60
1232
70
1271
80
1309
90
1347
100
1385
110
1423
120
1461
16.4
Pressure sensors
The pressure sensors in the refrigerant circuit connected to the WPM operate with a value of 4-20mA, a
Interruption is indicated in the display of the control unit with "---".
Read sensor values for high or low pressure via "Main menu / Info / Heat pump / Process data".
and check for plausibility. The values displayed in the controller are absolute pressures. Display values during
operation
/ Observe standstill and mechanically move line connections and joints. This can detect contact problems
or interruptions. If the sensor values change abruptly, the wiring or the sensor is defective.
16.5
Pressure socket connection Pressure monitoring

Table of Contents

Other manuals for STIEBEL ELTRON HPG-I 04 S Premium

Related product manuals