16.2 Inputs
In this submenu, the type of the sensor connected
can be adjusted for each individual input. The fol-
lowing types can be selected:
Switch
KTY
Pt500
RTA11-M
Pt1000
None
ATTENTION!
System damage!
Selecting the wrong sensor type
will lead to unwanted controller
actions. In the worst case, system
damage can occur!
Î Make sure that the right sen-
sor type is selected!
If KTY, Pt500 or Pt1000 are selected, the channel
Oset appears, in which an individual oset can be
adjusted for each sensor.
Î In order to select a sensor for the oset adjust-
ment, select the corresponding menu item by
pressing button
5
Î To adjust the sensor oset, select the desired
value by pressing buttons or
4
, then con-
rm by pressing button
5
In- / Outputs / Inputs
CS sensor oset
If a CS10 irradiation sensor is to be connected, an
oset has to be carried out before the connection is
made.
To carry out the oset, proceed as follows:
Î Adjust the CS type in the Type channel
Î Select the Oset channel
Î Conrm the reset enquiry with Yes
Î Select back to return to the Inputs menu, then
connect the CS sensor
Note:
When Grundfos Direct Sensors
TM
are used, the
sensor ground common terminal block must
be connected to PE (see chap. 2.2).
Adjustment
channel
Description Adjustment range / selection Factory setting
S1 ... S12 Sensor input selection - -
Type Selecting the sensor type
Switch, KTY, Pt500, RTA11-M,
Pt1000, None
Pt1000
Oset Sensor oset -15.0 ... +15.0 K 0.0 K
Imp. 1 ... 3 Impulse input selection - -
Type Selecting the sensor type
Impulse, Switch, KTY, Pt500,
RTA11-M, Pt1000, None
Impulse
Vol./Imp. Impulse rate 0.1 ... 100.0 1.0
CS10 CS10 input - -
Type CS type A ... K E
Oset Delete oset Yes, No No
Ga1, 2 Analog Grundfos Direct SensorTM - -
Type Grundfos Direct Sensor
TM
type RPS, VFS, None None
Min. Minimum pressure (if Type = RPS) 0.0 ... 0.5 bar 0.0 bar
Max. Maximum pressure (if Type = RPS) 0.1 ... 16.0 bar 0.6 bar
Min. Minimum ow rate (if Type = VFS) 1 ... 39 l/min 2 l/min
Max. Maximum ow rate (if Type = VFS) 2 ... 400 l/min 40 l/min
Gd1, 2 Digital Grundfos Direct SensorTM - -
Type Grundfos Direct Sensor
TM
type RPD, VFD, None None
if Type = VFD:
Measuring range selection
10 - 200 l/min, 5 - 100 l/min,
2 - 40 l/min, 2 - 40 l/min (fast),
1 - 20 l/min, 1 - 12 l/min*
1 - 12 l/min
* For the Inputs Gd1 and Gd2, the following sensor combinations are possible:
- 1 x RPD, 1 x VFD
- 2 x VFD, but with dierent measuring ranges only
295931-36390-8667 SOM 8 plus_en.indb 73 20.10.2011 13:14:58