44 |WPF | WPF cool www.stiebel-eltron.com
INSTALLATION
Maintenance
Fault display Cause Remedy
TO VALVE MFG Faulty communication between three-way valve and MFG. Check the communication cable terminal or replace the com-
munication cable.
TO BH MFG Faulty communication of the electric emergency/booster heater in the
MFG.
Check the communication cable terminal or replace the com-
munication cable.
TO MFG MFG timeout Check the communication cable terminal or replace the com-
munication cable.
ERR BH MFG The electric emergency/booster heater is faulty. Check the communication cable terminal or replace the com-
munication cable.
ERR PU SOL MFG Error brine pump MFG. Check the communication cable terminal or replace the com-
munication cable.
ERR VALVE MFG Error valve MFG. Check the communication cable terminal or replace the com-
munication cable.
ERR PU HC MFG Error heating circuit pump MFG. Check the communication cable terminal or replace the com-
munication cable.
17. Maintenance
We recommend an annual inspection (to establish the current
condition of the system), and maintenance if required (to return
the system to its original condition).