3. TECNICAL DETAILS
General
Product Identification Numbe
r
CE 0063 BP3254
Dimensions
(
h x w x d
)
M
m
835 x 458 x 485 890 x 458 x 670
Classification II2H3P
Gas Appliance Type B23; C13X,C23X,C33X,C43X, C53X, C63X,C83X
Boiler T
yp
e S-CB 60 80 100 120 150 180
Water content etc. Lt
r
3
,
9 5 6
,
5 8
,
3 10
,
4 12
,
9
Weight (empty) Kg 46 73 78 83 92 101
Gas connection R ¾” R ¾” R ¾” R ¾” R 1” R 1”
Co-axial flue connections m
80/125 80/125 100/150 100/150 100/150 100/150
Se
p
arate Flue Exhaust / Air Inle
t
80-80 80-80 100-100 100-100 130-130 130-130
Possible with Ada
p
tor
(
extra cost
)
mm
100-100 130-130
Power consum
p
tion W 355 355 355 375 460 460
Protection class IP40 IP40 IP40 IP40 IP40 IP40
Central heatin
g
N
ominal in
p
u
t
(
Nett
)
80/60ºC kW 14-56 18-74 23-92 27-111 34-138 43-166
N
ominal in
p
ut
(
Gross
)
50/30ºC kW 15-61 20-82 25-102 30-123 38-154 48-184
Gas flow max.
(
G20
)
m³/h
r
5
,
9 7
,
9 9
,
8 11
,
8 14
,
7 17
,
6
Efficienc
y
at 80/60ºC % 97 98 98 98 98 98
Efficienc
y
50/30ºC % 109 109
,
5 109
,
5 109
,
5 109
,
5 109
,
5
Efficienc
y
40/30ºC RAL 61 % 109
,
5 110 110 110 110 110
N
ominal out
p
ut at 80/60ºC kW 55 73 90 109 136 163
N
ominal out
p
ut at 50/30ºC kW 15-60 20-80 25-100 30-120 36-150 45-180
N
orm efficienc
y
75/60ºC RAL-UZ61 107 107 107 107 107 107
NO x emission, RAL 61 mg/kWh <15 <15 <15 <15 <15 <15
CO emission, RAL 61 mg/kWh <20 <20 <20 <20 <20 <20
Table 1: Data
Boiler control includes:
Cascade control for up to 8 boilers ( requires flow temperature sensor at extra cost ) see item G page 8
Remote run & fault indication
0-10 VDC control connection ( requires flow temperature sensor at extra cost )
Control for external calorifier primary pump ( pump not included ) via relay at extra cost ( see page 22)
Weather compensation control (with outside detector at extra cost)
Control for an external pump via relay at extra cost,( see page 22 )external pump not included.
Electronic Ignition.
Boiler output modulated between 25% and 100%,
Data
CO2- flue
g
as % 9
Dew
p
oint combustion
g
as °C 53
Tem
p
. Flue
g
as
@
ambient tem
p
20ºC °C 85
Flue resistance ca
p
abilit
y
* Pa 250* u
p
to 600*
PH value condensate 4 to 5
,
5
Available
p
ressure at 25ºC mw
k
2
,
5 3 1
,
5 1
,
5 1
,
5 1
,
5
Max. flow tem
p
. °C 90
Min./Max. Boiler Pressure
b
a
r
0.5
6
Sound level at Maximum Output
dBA 46.0 47.0 48.0 49.0 50.0 50.0
Average Sound level
dBA 32.0 33.0 33.0 34.0 35.0 35.0