E/0310/50/17
Reheat 1 Start Value
Reheat 1 + 2 Hysteresis
Reheat 2 Start Value
Parameters of reheat's stages 1+2 can be entered in these items
The hysteresis is valid for both stages.
Humidification Start Value
Humidification Hysteresis
Parameters of 2-point-humidification can be entered in these items.
Dehumidification Start Value
CW-units:
For dehumidification CW-valve opens to the indicated opening degree entered in item
11a.
Units with compressor:
The dehumidification circuit and the compressor will be started.
The "dehumidification" function is stopped when temperature is less than 0.5 K (0.9R) above
the low temperature limit value. It is enabled with a hysteresis of 0.5 K (0.9R).
Modification from version 2.1:
3K (5R) underneath the temperature setpoint the dehumidification is stopped. This way
a fall of the room temperature by keeping the humidity setpoint is avoided.
Hysteresis Dehumidification
Parameters for dehumidification are entered in this item.
If the hysteresis of humidification and dehumidification is set to zero, the
limit value "humidity" is not supervised.
The values of the items 9a+b, 11b, 12, 14, 15, 17 are entered as a difference to
the setpoint.
Item
12
13
14
15
16
17
18