2.6
CONTROL SYSTEM, 
FUNCTIONAL DESCRIPTION
Refer to Figure 2-5 and Figure 2-6. The purpose of the 
compressor control system is to regulate the amount of air 
being compressed to match the amount of compressed air 
being used. The capacity control system consists of a 
solenoid valve, regulator valve and an inlet valve. The 
functional description of the control system is described 
below in four distinct phases of operation. For explanatory 
purposes, this description will apply to a compressor with 
an operating range of 100 to 110 psig 
(6.9 to 7.6 bar). A 
compressor with any other pressure range would operate 
in the same manner except stated pressures.
Start Mode - 0 to 50 PSIG 
(0 to 3.5 Bar)
When the compressor " " (START) pad is depressed, 
the receiver tank pressure will quickly rise from 0 to 50 psig 
(0 - 3.4 bar). The compressor initially starts unloaded with 
the solenoid valve open and the inlet valve closed. It then 
switches to full load when full rpm has been achieved. 
During this period, both the pressure regulator and the 
solenoid valve are closed, the inlet valve is fully open and 
the compressor pumps at full rated capacity. The rising 
compressor air pressure is isolated from the service line 
in this phase by the minimum pressure valve set at 
approximately 50 psig (3.4 bar).
7
6
5
4
8
2
3
1
SU_0000007
9
1. Air Outlet
2. Unload Solenoid Valve
3. Pressure Regulator
4. Air Inlet
5. Blowdown Valve
6. Minimum Pressure/Check Valve
7. Receiver Tank
8. Sequencing Solenoid Valve
9. WS Controller
Figure 2-5: Standard Sequencing Control System
SECTION 2
12
3000-4500 Operator’s Manual and Parts List
®SULLAIR®