Water-Cooled Compressors
Adequate cooling water flow must be supplied to water-
cooled compressors. Water delivery must be verified to 
assure constant delivery of the volumes outlined in Table 
4-1 Water Flow Requirements on page 52. The figures 
shown are for full-load operation utilizing an aftercooler. 
Cooler water will reduce water-flow requirements and 
warmer water will increase water-flow requirements.
Water piping to and from the compressor unit must be a 
minimum of 1 inch diameter. Isolation valves with side 
drains should be installed on both input and return lines. 
Input water should have a 2 mm strainer installed in-line. 
A normally closed solenoid valve should be connected to 
the water outlet of the compressor. The compressor 
control circuit switches this circuit. Consult the Sullair 
Service Department for assistance in these setups.
Water quality is critical to proper cooling of the 
compressor. Excessive build-up of lime, scale or other 
deposits can restrict the flow of water to the compressor. 
These deposits act as a thermal insulator and reduce the 
efficiency of the water cooler.
The cleaning of piping and water coolers is the customer’s 
responsibility. Inspect all piping for deposits and clean as 
necessary. Refer to 
Water Quality Recommendations on page 53.
TABLE 4-1 WATER FLOW REQUIREMENTS
Water Temp 
˚F/˚C
Water Flow
Gallons Per Minute /Liters Per Minute (l)
40HP/30kW 50HP/37kW 60HP/45kW
70/21 5.6 7.0 (26.5) 9.0 (31.6)
80/27 8.4 10.5 (35.7) 11.5 (41.6)
(I) Water pressure should be maintained between 25 and 75 
psig (1.7 and 5.2 bar), but not to exceed 145 psig (10 bar)
Table 4-2 Ventilation Requirements on page 53
indicates the minimum ventilation requirements 
necessary to keep the compressor running at its normal 
operating temperature. The fan air requirement is the 
amount of air, which must flow through the compressor for 
proper ventilation. The heat rejection requirement is the 
amount of heat that is radiated by the compressor. This 
heat must be removed to assure a normal operating 
temperature. With air-cooled compressors it is possible to 
use this heat for space heating, providing additional 
pressure drop across the fan does not exceed 0.2 in H
2
O. 
Consult a Sullair office for assistance in utilizing this heat. 
If ductwork is added, the high static fan option is required.
DO NOT install a water-cooled or an air-cooled/after-
cooled compressor where it will be exposed to 
temperatures less than 32˚F (0˚C). Consult factory for 
machine operation in ambient temperature less than 32˚F 
(0˚C).
If machine is equipped with water regulating valve, use the 
water regulating valve to adjust compressor temperature 
to maintain a minimum of 180°F (82.2°C); 190°F (87.8°C) 
for 24KT.
Temperature and pressure gauges should be installed in 
the water piping for use in troubleshooting of the water 
system. Water pressure should ideally be between 25 and 
75 psig (1.7 and 5.2 bar) but must not be above 145 psi 
(10 bar).