Section 5
OPERATION
24
lected.
UNITS
ENGLISH
S Communications ID # --- This is the net-
work address of a machine. If there is more
than one machine connected to the net-
work, each machine must have a unique
number.
COM ID #
1
S Communications baud rate --- T h i s
should always be selected to 9600 baud
for all sequencing modes. It may be lower
for slave or monitoring modes.
BAUDRATE
9600
S Sequence method --- T h i s p a r a m e t e r s e t s
the method used for optional sequencing.
ThechoicesareDISABLED,REMOTE,
SLAVE, HOURS, COM ID#. See the Se-
quencing & Protocol Manual (See Recom-
mended Spare Parts List) for details about
these modes.
SEQUENCE
HOURS
S Drain interval --- The time between actua-
tion of the drain valve.
DRN INTV
10 MIN
S Drain time --- The amount of time that the
drain valve is actuated.
DRN TIM
1SEC
S Last Communication Number --- U s e d
only for sequencing, see Sequencing &
Protocol Manual for details.
LAST COM
3
S Lowest Allowable Pressure --- U s e d o n l y
for sequencing, see Sequencing & Proto-
colManualfordetails.
LOWEST
90 PSI
S Recovery Time --- Used only for sequenc-
ing, see Sequencing & Protocol Manual for
details.
RECOVER
10 SEC
SRotate T ime --- Used only for sequencing
--- units in HOURS, see Sequencing & Pro-
tocolManualfordetails.
ROTATE
50 HOURS
SMachine Capacity --- U s e d o n l y f o r s e -
quencing --- units in CFM (M
3
/min), see Se-
quencing & Protocol M anual for details.
CAPACITY
100
S Sequence Hours --- U s e d o n l y f o r s e -
quencing, see Sequencing & Protocol
Manual for details.
SEQ HRS
1000
5.8 OPERATING THE COMPRESSOR
Before operating the compressor t he operating pa-
rameters must be setup. See the previous section
on operating parameter setup.
MANUAL OPERATION MODE
In this mode the compressor will run indefinitely, as
long as temperatures and pressure remain within
the valid operating ranges, and the motor overload
or emergency stop contacts are not tripped. Press-
ing the “I” will turn on the compressor and put it in
manual mode. If the compressor is already run-
ning, but in automatic mode, pressing “I”will
switch operation to manual. Pressing “I”whileal-
ready running in manual mode will cause the Su-
pervisor to turn off t he common fault relay, if en-
gaged, and clear any maintenance indicators.
To stop the compressor, press “O”Ifthecompres-
sor is already off when “O” is pressed, the common
fault relay will be turned off, if engaged, and it will try
to clear the alarm and maintenance indicators. Re-
gardless of what the compressor is doing, pressing
“O” puts the Supervisor in manual stop mode.