1. Install the air compressor inside a room with adequate space, ventilation and relatively low humidity.
2. Keep the operating room temperature between 32
°
F and 104
°
F (0
°
C and 40
°
C).
3. Install the air compressor with the recommended spacing shown in the figure below for ease of 
    maintenance and temperature control.
 ・The air compressor is designed to intake air from the left side of the package and exhaust the air out 
      of the top of the package. Provide suction and exhaust openings as shown in the figure below to
      properly ventilate the room. If the suction and exhaust openings cannot be provided, do not modify
      the air compressor without consulting the local Sullair distributor.
4. The allotted space located to the right and to the rear of the air compressor must be maintained
    to perform maintenance. Ensure that this space is maintained if the air compressor is going to be
    permanently installed. (#)
A B
Installation(continued)
5
 3  Installing the Air Compressor
Ventilating fan
● If the temperature exceeds 104
°
F (40
°
C) in
    the room, install a ventilating fan to keep
    the room temperature below 104
°
F (40
°
C).
● Select a ventilating fan with enough
    capacity to handle the air flow of the room.
Maintenance Space,
Intake Air, Discharge 
Piping and Wiring
● Secure enough space for proper ventilation.
● Absence of intake space causes the suction resistance to
    increase, resulting in temperature rise in the package, which may
    cause a reduction in the life of air compressor components.
● Secure enough space for wiring and piping.
Ventilation and 
Exhaust Space
● Secure enough space for proper 
    ventilation.
● Absence of intake space causes
    the suction resistance to increase,
    resulting in temperature rise in the
    package, which may cause a
    reduction in the life of air
    compressor components.
Maintenance Space for
Right & Rear Sides
● If a space of more than 12 in
   (305 mm) for the right side and
   20 in (508 mm) for the rear
   cannot be secured, utilize a piping
   connection that can be easily
   removed for maintenance.
Front Maintenance Space
● Secure the proper amount of
    space to open the front door of
    the air compressor for inspection.
Exhaust duct
● Do not directly connect the duct with the
    air compressor. The ducting hood should
    maintain a distance (indicated as “h”)
    between the air compressor and the duct
    that is larger than the diameter of the duct.
h
Exhaust
air
40 in.(1016 mm)
or more
Exhaust
Opening
Intake
Opening
Exhaust
air
I
ntake
air
I
ntake
air
12 in.(305 mm)
or more (#)
20 in.(508 m m)
or more (#)
Exhaust
air
40 in.(1016 mm)
or more
25 in.(635 mm)
or more
Intake Opening
● The intake opening should be installed as
    low as possible. The area of the opening
    should be calculated as 1,550 sq in.(1m
2
)
    per compressor.
● Conditions of the ambient air, including
    dust and toxic substances, should be
    considered when selecting the location
    for the intake air opening.
【Reference】
■ Guidance for construction of ventilating fan and exhaust duct
Exhaust Air
Exhaust Air
of air
compressor
Intake Air
■ Ventilating Fan
Refer  to  the  volume  of 
necessary ventilation (1).
Intake Air
Exhaust 
Duct
■ Ventilating Fan
Refer  to  the  volume  of 
necessary ventilation (2).