SUPERVISOR CONTROLLER™ USER MANUAL SECTION 2
12
The four pressures P1, P2, P3 & P4 as well as the
differential pressure dP1 can be calibrated. The
number on the right hand side of the line is added to
the transducer reading to give the calibrated reading.
The calibrated reading is shown in the middle of the
line.
Cap and KW calibration (VSD packages only) may
be used to adjust values shown on VSD Status
displays. These are factory set to nominal values
(100%), but may be adjusted as desired.
There are also three other parameters in the
calibration function:
Protect—When set to yes, protects the control
parameters from change.
Fault on Warn—Force fault on warning.
Force Unload—When set to yes, forces the machine
to unload.
2.12 TEST
Used by Sullair personnel for troubleshooting of
serial communications.
2.13 FACTORY SETUP- MODEL
SETTINGS.
The factory setup display is used by Sullair personnel
to initially set up the machine. The following values
reflect the machine configuration.
Model—Model number of machine.
Cooling—Air or Water.
Press Trans—Pressure transducer range 200, 250,
500.
P1 Max—Maximum discharge pressure.
KT Fluid—Yes or No, indicating fluid.
Water Switch—Water pressure switch, Yes or No.
Oil Switch—Oil pressure differential switch, Yes or
No.
Min Load Psi—Minimum acceptable load P1
pressure setting. Separator Maintenance warning is
disabled for loaded P1 pressures below this value
(i.e., during start-up).
Lube Cycle—Pre-lube/ Post-lube function timer - 0
seconds (disabled) to 30 seconds.
K8 Option—K8 output relay function selector—
Disabled, Oil pump prelube and postlube control,
Master Control for special external sequence control.
Stop Timer—Time to run machine before stopping.
Protect—Protect control parameters.
Load Hours—Hours machine was running and
loaded.
Run Hours—Hours machine was running loaded
and unloaded.
Load Cycles—Number of load/unload cycles.
Starts—Number of machine starts.
Capacity—Maximum capacity of machine.
Spiral Valve—(VSD packages only) Yes or No,
indicating spiral valve control.
VSD- Describes signal from Supervisor controls to
the VSD controls:
None—No VSD
Pressure—The Supervisor pressure signal is
connected to a drive analog input
Serial—The drive is connected on the
Supervisor serial data bus
Speed—The Supervisor provides a speed
signal to a drive analog input.
Com Module—Yes/No Enables or disables the
communication module if installed.