SUPERVISOR CONTROLLER™ USER MANUAL SECTION 4
22
Table 4-2: Analog Alarms (Flooded Screw Compressors Less Than 200 psi)
Sensor Type Limit Start Delay Run Delay Check (*) Comment
P_1 HIgh Inhibit 5 0 0 At Start High sump psi at start
P_1 Low Fault 5 0 0 When Running Immediate Fault
P_1 High Fault 500 0 0 Constantly Sensor failure fault
P_2 High Fault 500 0 0 Constantly Sensor failure fault
P_3 High Fault 500 0 0 Constantly Sensor failure fault
P_4 High Fault 500 0 0 Constantly Sensor failure fault
T_1 Low Fault -40 0 0 Constantly Sensor failure fault
T_1 High Fault 225 5 30 Constantly Delayed for temp spikes
T_1 High Fault 235 5 30 Constantly Delayed for temp spikes
T_1 High Fault 245 0 0 Constantly Immediate Warning
T_1 High Fault 255 0 0 Constantly Immediate Fault
T_1 High Fault 500 0 0 Constantly Sensor failure fault
T_2 Low Fault -40 0 0 Constantly Sensor failure fault
T_2 High Warn 225 5 30 Constantly Delayed for temp spikes
T_2 HIgh Fault 235 5 30 Constantly Delayed for temp spikes
T_3 Low Warn -40 0 0 Constantly Sensor failure warning
T_3 High Warn 500 0 0 Constantly Sensor failure warning
T_4 Low Fault -40 0 0 Constantly Sensor failure fault
T_4 HIgh Fault 500 0 0 Constantly Sensor failure fault
(*) In the ‘Check’ column above, alarms are checked:
Constantly—if machine running or stopped
When Running—if machine is running
If Enabled—if parameter is non-zero
At Start—will not allow start if alarm present
Over Min Psi—machine is loaded and above min load pressure