SECTION 4 SUPERVISOR CONTROLLER™ USER MANUAL
27
Table 4-5: Machine Power Outage Behavior
Seq. Mode
Local/
Remote
Remote
Start/
Stop
Run Mode Action (State)
Disabled xxxx xxxx Cont Manual Stop
Disabled xxxx xxxx Auto Start after Restart delay & P2 < Load psi, & P1 < 5 psig
Remote Local xxxx Cont Manual Stop
Remote Local xxxx Auto Start after Restart delay & P2 < Load psi, & P1 < 5 psig
Remote Remote Off Cont Remote Stop
Remote Remote Off Auto Remote Stop
Remote Remote On Cont Start after Restart delay
Remote Remote On Auto Start after Restart delay & P2 < Load psi, & P1 < 5 psig
Note: ‘xxxx’ means ‘has no effect’.
Table 4-6: Remote Start/Stop Input
Local/Remote
Remote
Start/Stop
Run
Mode
Action (State)
Local xxxx Cont Normal Cont Operation
Local xxxx Auto Normal Auto Operation
Remote Off Cont Remote Stop
Remote Off Auto Remote Stop
Remote On Cont Start if stopped
Remote On Auto Normal Auto Operation