WSPC USER INTERFACE MANUAL SECTION 4
30
parameter can be adjusted at the Adjustments
Display to assign the compressor to run in a specific
order in the sequence system. When the operating
mode is set to Automatic, the machine with the
lowest number of sequence hours will be the next to
start and the machine with the highest number of
sequence hours will be the next to stop.
PSI—displays the output pressure of the related
compressor. This may be displayed as BAR or Kpa
depending on user profile preferences. This
measurement is taken at the P2 pressure transducer
of the compressor and may be a different value than
the overall system pressure.
ACFM—shows the capacity of the specific
compressor. Capacity is the volume of air in cubic
feet per minute (cfm) being delivered by the
compressor.
Remote—indicates whether the compressor
operation is being controlled remotely (including
sequencing control) or by the local controller only.
Service—displays “Yes” when the compressor is in
need of service. This indication is accompanied by
either a service reminder or warning message to
inform the user of the nature of the service required.
Refer to the WS Controller Sequencing and Protocol
Manual for details on operating compressors in
sequence.
4.8 ADJUSTMENTS DISPLAY
Both the compressor control parameters and
sequencing parameters can be edited at the
Adjustments display of the WSPC User Interface.
SeeFigure 4-11. At this display the user can view the
current settings of the machine control parameters
and make adjustments as necessary. Changes to the
control parameters will be reflected at the WS
Controller located on the compressor.
Figure 4-11: Control Parameter Adjustments Display