Commissioning is the process of initializing the WS
Controller for operation with a specific compressor
model and type. During the commissioning process,
all previous stored data (parameter values, logs,
history information, etc.) is erased from the controller
memory. The new default parameter values are then
loaded to the controller that configure it for a
particular compressor model and application.
To commission a controller for a compressor model:
1. Press the emergency stop button and leave
it depressed throughout the commissioning
procedure.
2. On the Menu Bar select the “File” menu and
click “Commission” in the drop-down option
list. See Figure 7-2. The “Commission” win-
dow will be presented.
NOTE
Controller commissioning is normally a
one-time event when a new controller is
installed.
The compressor must be stopped before
beginning the commissioning process.
When the compressor is running, the
“Commission” option is inoperable.
NOTE
Depending on the selected model, the
commissioning procedure may alter the
functions of inputs and outputs. Depress
the Emergency Stop button to prevent
output relays from operating inappropri-
ately during the process.
Figure 7-2: Commission Option