WSPC USER INTERFACE MANUAL SECTION 7
62
MAXIMUM USER UNLOAD SETTINGS
The Maximum User Unload settings allow the
maximum limit to be set for the compressor unload
pressure. These limit the setting for the User-level
adjustment of unload pressure.
Refer to Figure 7-10.
Load/Unload Mode—Sets the maximum Unload
pressure limit for the compressor when the machine
is operated in Load/Unload mode.
Modulating Mode—Sets the maximum Unload
pressure limit for the compressor when the machine
is operated in Modulating mode.
DISABLE WARNING RESET
Current versions of WS Controllers reset warnings
whenever the start or stop button is pressed on the
keypad. The administrator may disable this feature,
and require all warnings to be reset by WSPC only.
Refer to Figure 7-10.
1. Select the “Start Button” check box to disable
reset by the start button.
2. Select the “Stop Button” check box to disable
reset by the stop button.
ASSIGNING DIGITAL INPUTS
To make adjustments at the “Admin” Display (Refer
to Figure 7-11):
1. Click at the WSPC
to connect communication between the com-
puter and the WS Controller. Connection
must be enabled before adjustments can be
made at the Admin display.
2. Press (Stop) at the controller to
stop the compressor operation. The com-
pressor must be stopped before adjustments
can be made at the Admin display.
3. Click on the drop-down arrow at the right of
the row containing the name of the function
to be reassigned.
4. In the drop-down list, select the input to
assign to the corresponding function. The
new assignment will become active a few
seconds after entry.
AI0 AI1 AI2 AI3 AI4 AI5 Separator
Temp 1Temp 2Temp 3
Sump
Pressure
Line
Pressure
Other
Pressure
(Sump-Line)
Pressure