9 Grid Dispatching Function User Manual
64
Disable
If the grid company does not need the power plant to adjust the voltage at the
grid-connection point, and the inverter does not need to cooperate with the grid for
reactive power compensation, the inverter can keep operating in the pure active
power output state, and the operator can set the "Reactive control mode" to
"Disable" to forbid reactive power derating.
Remote power control
Set the "Reactive control mode" to "Remote power control".
Control method includes "Open loop control" and "Closed-loop control".
Local power control
Set the "Reactive control mode" to "Local power control".