EasyManuals Logo

Sungrow SG30CX-NI User Manual

Sungrow SG30CX-NI
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #118 background imageLoading...
Page #118 background image
108
Parameters
SG30CX SG33CX
Efficiency
Max. efficiency / Euro-
pean efficiency
98.6% / 98.3%
Protection
DC
reverse polarity protection
Yes
AC short circuit
protection
Yes
Leakage current
protection
Yes
Grid monitoring
Yes
Ground fault monitoring
Yes
DC switch
Yes
AC switch
No
PV string monitoring Yes
Q at night function
Yes
PID recovery function
Yes
Arc fault circuit interrupt-
er (AFCI)
Optional
Overvoltage protection
DC Type II / AC Type II
DC Type II (Optional:Type I +
II) / AC Type II
General Data
Dimensions (W×H×D)
702×595×310mm
Weight
50 kg
Topology Transformerless
Degree of protection
IP66
Night power
consumption
≤2 W
Operating ambient tem-
perature range
-30 ~ 60 (> 45 derating)
Allowable relative humid-
ity range
0 ~ 100%
Cooling method
Smart forced air cooling
Max. operating altitude
4000 m (> 3000 m derating)
Display
LED, Bluetooth + App
Communication
RS485 / Optional: WLAN ,
Ethernet
RS485 / Optional: WLAN,
Ethernet
DC connection type
MC4 (Max. 6 mm
2
)
10 Appendix User Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG30CX-NI and is the answer not in the manual?

Sungrow SG30CX-NI Specifications

General IconGeneral
BrandSungrow
ModelSG30CX-NI
CategoryInverter
LanguageEnglish

Related product manuals