5.4 Crimp OT/DT terminal
Crimp OT/DT terminal
1. Heat shrink tubing 2. OT/DT terminal
3. Hydraulic pliers 4. Heat gun
Aluminum Cable Requirements
If an Aluminum cable is selected, use a copper to Aluminum adapter terminal to avoid direct
contact between the copper bar and the Aluminum cable.
figure 5-2 Aluminum Cable Connection
1. Copper to Aluminum adapter terminal 2. Flange nut 3. Aluminum cable
Ensure that the selected terminal can directly contact with the copper bar. If there
are any problems, contact the terminal manufacturer.
Ensure that the copper bar is not in direct contact with the aluminum wire. Other-
wise, electrochemical corrosion may occur, impairing the reliability of electrical
connection.