111
Parameters
SG40CX SG50CX
Allowable relative humid-
ity range
0 ~ 100%
Cooling method
Smart forced air cooling
Max. operating altitude
4000 m (> 3000 m derating)
Display
LED, Bluetooth + App
Communication
RS485 / Optional: WLAN,
Ethernet
RS485 / Optional: WLAN,
Ethernet
DC connection type
MC4 (Max. 6 mm
2
)
AC connection type
OT or DT terminal (Max.70 mm
2
)
Grid Support
Q at night function, LVRT, HVRT, active & reactive power con-
trol and power ramp rate control
Note(3): The inverter enters the standby state when the input voltage ranges between 1,000
V and 1,100 V. If the maximum DC voltage in the system can exceed 1000 V, the MC4 con-
nectors included in the scope of delivery must not be used. In this case MC4 Evo2 connec-
tors must be used.
Note(4):
The voltage difference between MPPTs should be less than 80 V.
The voltage of the configured string should be higher than the lower limit of the rated
MPPT voltage.
Parameters
SG30CX
(5)
SG50CX
(5)
Input (DC)
Recommended max. PV
input power
45 kW 76 kW
Max. PV input voltage
1100 V
(6)
Min. PV input voltage /
Start-up input voltage
200 V / 250 V
Nominal PV input
voltage
585 V
MPP voltage range 200 V ~ 1000 V
MPP voltage range for
rated power
550 V ~ 850 V
(7)
No. of independent MPP
inputs
3 5
No. of PV strings per
MPPT
2
Max. PV input current
78 A (26 A / 26 A / 26 A)
130 A (26 A / 26 A / 26 A /
26 A / 26 A)
User Manual 10 Appendix