Refer to “Protection Parameter Setting” in User Manual for country code explanation.
If the inverter is installed where the country code is not included, please choose
item “Other” and manually set the protection parameters.
Step 6 If the country code set as GR, a Grid codes
page as shown in the right will appear. Press
to select grid code and press ENTER to
confirm.
If the country code set as DE, a Grid codes page as
shown in the right will appear, where LV signifying
low-voltage grid; MV signifying medium-voltage
grid. Press
to select grid code and press ENTER to
confirm.
If the country code set as TK, a Grid codes page as
shown in the right will appear. Press
to select grid
code and press ENTER to confirm.
If the country code set as TH, a Grid codes page
special for Thailand will appear. Press
to select
grid code and press ENTER to confirm.
After setting the Country parameter, please proceed to set other
parameters of the
inverter in accordance with the specific requirements
of the local grid. Before commissioning, please check thoroughly if the
set parameters meet the local grid requirement.