General Data Center Environmental Specications




Conductive dust: Air should be free of conductive dust, zinc whiskers, or other conductive particles.
Corrrosive dust: Air should be free of corrosive dust.


TC 9.9

TC 9.9
*If testing with silver or copper coupons results in values less that 200 Å/month or 300 Å/month, respectively, then operating
up to 70% relative humidity (RH) is acceptable. If the testing shows corrosion levels exceed these limits, then catalyst-
type pollutants are probably present and RH should be driven to 50% or lower.