Chapter 6 Function & Setting (P400)
www.supmea.com
19
OFT
The zero offset value of the
transmitter's main variable,
which is superimposed on the
main variable. Zero point
transfermation of transmitter
can be realized.
GAI
The gain coefficient of the main
variable does not perform gain
corrections to offset and reset
values.The resolution is
0.0001FS, which aims of
perform secondary calibration
for the customer.
FIL
The value od filtering and
damping are set to a maximum
of 30 and a minimum of 0.The
larger the value, the stronger
the filtering effect.
SOL
The modification of board card
4mA calibration is to observe
the current of the external
ammeter, and the modification
of the data and adjustment of
the ampere meter current can
receive an accurate 4mA.