Using specialized tools to check detector sensitivity.
Using the detector's built-in switch to perform a functional test.
Using a test card and aerosol to check detector sensitivity.
Best practices for wiring smoke detectors to control panels and other devices.
Step-by-step procedure for installing the smoke detector.
Procedures for verifying the correct operation and sensitivity of the smoke detector.
This document describes several models of direct wire smoke detectors from System Sensor, including ionization and photoelectronic types, with and without fixed heat detection and audible signals.
The System Sensor 1400 series consists of dual-chamber ionization smoke detectors that utilize state-of-the-art, unipolar sensing chambers. These detectors are designed for open area protection and are compatible with UL-listed, 2-wire control panels. They feature a latching alarm that can only be reset by a momentary power interruption. An integrated LED provides local visual status indication, blinking every ten seconds in standby and lighting continuously in alarm. These detectors also offer a provision for connecting an optional Model RA400Z Remote Annunciator, which provides a supplementary visual alarm indication and mounts to a single gang box.
The System Sensor 1412 and 1424 models are dual-chamber ionization smoke detectors designed for open area protection and use with UL-listed, 4-wire control panels. The 1412 operates at 12VDC, and the 1424 operates at 24VDC. Like the 1400 series, they are latching type system detectors, requiring a momentary power interruption to reset. An LED blinks every 10 seconds in standby and latches on continuously in alarm. Each detector includes one Form A (SPST-NO) contact for the alarm-initiating circuit and one Form C (SPDT-NO/NC) set of auxiliary contacts. Power supervision is achieved by installing a Power Supervisory End-of-Line Relay Module (A77-716) at the end of the detector power loop. A power failure or break in the loop de-energizes the EOL Module, triggering a trouble signal at the control panel.
The System Sensor 2400 and 2400TH are photoelectronic smoke detectors that use state-of-the-art, optical sensing chambers. They are designed for open area protection and are compatible with UL-listed 2-wire control panels. The 2400TH model additionally features a restorable, built-in, fixed temperature (135°F) thermal detection unit. These detectors are UL 268 listed and are latching type, requiring a momentary power interruption for reset. An LED blinks every 10 seconds in standby and latches on continuously in alarm. They also provide an output for connecting an optional Model RA400Z Remote Annunciator.
The System Sensor 2412AT, 2424AT, and 2424AIT are photoelectronic smoke detectors with fixed heat detection, listed to UL 268, and designed for open area protection with UL-listed, compatible, 2-wire control panels. The 2412AT operates at 12 VDC, while the 2424AT and 2424AIT operate at 24 VDC. These sensors utilize a light scattering principle with a unique photo-optic sensing chamber. They include restorable 135°F fixed-temperature heat detection. The 2400AT and 2412AT/2424AT heat detection units are integrated with the photoelectronic sensor, while the 2424AIT's heat detection unit is isolated and can be monitored separately. Additionally, a piezoelectric horn in each detector produces an interrupted, 85 dBA tone when the individual detector alarms or when the supply voltage polarity is reversed. An LED provides a local alarm indication, remaining on when the supply polarity is reversed. A screw terminal is provided for a remote LED annunciator (RA400Z). These are latching type detectors, reset by momentary power interruption. Each detector contains one Form A (SPST-NO) contact for the alarm-initiating circuit and one set of Form C auxiliary contacts. Power supervision is achieved by installing a Power Supervisory End-of-Line Relay Module (A77-716) at the end of the detector power loop.
| Type | Photoelectric |
|---|---|
| Power Source | 24V AC/DC |
| Voltage | 24V |
| Alarm Volume | 85 dB at 10 feet |
| Operating Temperature Range | 32°F – 120°F (0°C – 49°C) |
| Height (including base) | 2.0 inches |
| Agency Listings | UL 268 |
| Alarm Indicator | Red LED |
| Compatibility | Compatible with listed control panels |