Mainmenuitem
Sub-menuitem1Sub-menuitem2
Explanations
Controltemp
Supplyair
control
P-band:33.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Supplyaircontrolfunction
Note:
SeeCorrigoEventilation
manualfordeeperexplanation
Roomcontrol
P-band:
100.0°C
I-time:300.0
sec
SetP-bandandI-timeforthe
Roomcontrolfunction
Note:
SeeCorrigoEventilation
manualformoreinfo
Shutdownmode
P-band:
100.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Shutdownfunction
Note:
SeeCorrigoEventilation
manualfordeeperexplanation
Frost
protection
Active
Setpshutdown:
25.0°C
P-bandactive:
5.0°C
P-bandactiveCmeansthat
thefrostprotectioncontroller
willstartoverridingtheheating
outputwhenthefrostprotection
temperatureislessthan5
degreesabovethesetfrost
alarmdefaultalarmlimitisC
Faststop
atfrost
protection
alarm
Yes
Setthefaststopoftheunitin
caseoffrostprotectionalarmto
YesorNo.
Controlflow
AlternativelyPressure
controlifchoseninthe
congurationoftheunitfrom
factory
Flowcontrol
SAF
P-band:
10000.0m³/h
I-time:10.0
sec
Min.output:
0%
SetP-band,I-timeandMin.
outputforthesupplyair
fanwhentheunitcomes
conguredasFlowcontrol
fromfactory.Alternatively
Pressurecontrolifthat
congurationischosen
TopvexSR09,11,TR09-15OperationandMaintenanceInstructions
207880
17
SystemairAB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Topvex SR 09 and is the answer not in the manual?

SystemAir Topvex SR 09 Specifications

General IconGeneral
BrandSystemAir
ModelTopvex SR 09
CategoryAir Handlers
LanguageEnglish

Related product manuals