Explanations
→Controltemp
Supplyair
control
P-band:33.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Supplyaircontrolfunction
Note:
SeeCorrigoEventilation
manualfordeeperexplanation
Roomcontrol
P-band:
100.0°C
I-time:300.0
sec
SetP-bandandI-timeforthe
Roomcontrolfunction
Note:
SeeCorrigoEventilation
manualformoreinfo
Shutdownmode
P-band:
100.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Shutdownfunction
Note:
SeeCorrigoEventilation
manualfordeeperexplanation
→Frost
protection
Active
Setpshutdown:
25.0°C
P-bandactive:
5.0°C
P-bandactive5°Cmeansthat
thefrostprotectioncontroller
willstartoverridingtheheating
outputwhenthefrostprotection
temperatureislessthan5
degreesabovethesetfrost
alarmdefaultalarmlimitis7°C
Faststop
atfrost
protection
alarm
Yes
Setthefaststopoftheunitin
caseoffrostprotectionalarmto
YesorNo.
→Controlflow
AlternativelyPressure
controlifchoseninthe
congurationoftheunitfrom
factory
Flowcontrol
SAF
P-band:
10000.0m³/h
I-time:10.0
sec
Min.output:
0%
SetP-band,I-timeandMin.
outputforthesupplyair
fanwhentheunitcomes
conguredasFlowcontrol
fromfactory.Alternatively
Pressurecontrolifthat
congurationischosen