4.3MenuoverviewOPERATOR/SERVICELEVEL
BelowmenuoverviewshowsboththeOperatorandServicelevel.Theoverviewofthepartsuniqueto
theServicelevelinbelowtablearemarkedwithgreybackgroundcolor.T ologontotheServicelevel
usecode2222underAccessrights.
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Explanations
TR03ELflow
2010–03–1509:00
System:Stopped
Sp:18.0Act:ºC
Startscreenheadline
Canbesetto5differentlayouts
(Changeableat“systemlevel”
undertheconfiguration
menu.Standardcodefrom
factorytoentersystemlevelis
3333.)
→Runningmode→RunningmodeRunningmode
Auto
SetRunningmodetoAuto,
OnorOff
Runningtime
SAF:0.0h
EAF:0.0h
Showsthetimeinhoursthat
themotorshavebeenoperating
SAF=Supplyairfan
EAF=Exhaustairfan
→Selected
functions
Control
function
Extractair
control
Fancontrol
Flowcontrol
Showstypeofairtemperature
controltheunitisconguredfor.
Showstypeoffanspeed
controltheunitisconguredfor
Heating:Water
Exchanger:
Rot.Excha
Cooling:Water
Showstypeofheatingselected
Showstypeofexchanger
selected
Showstypeofcoolingselected
Freecool
active:No
Showsthestatusofthefree
coolingfunction
Supportcontrol
Active:No
CO2/VOCactive
Never
Showsthestatusofthesupport
controlfunction
Showsthestatusofthe
demandventilation(CO2/VOC)
function
Firedamper
function
Notactive
Operationwhen
alarm
Stopped
Showsthestatusofthere
damperfunction
TopvexSR09,11,TR09-15OperationandMaintenanceInstructions
207880
10