EasyManua.ls Logo

T.E.L.L. EAG80 - 8 Commissioning EAG80; 8.1 Theoretical adjustment of scales; 8.2 Input of time and date; 8.3 Settings for printers or large-size displays

T.E.L.L. EAG80
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Total no. of pages: 30
PAGE 27
Anleitung EAG80_26_00_2017_03_28_GB
Version 28.04.2017
8 Commissioning EAG80
Steps 1 to 4 are normally already set.
8.1 Theoretical adjustment of scales
Settings under 4.4.1
AuFLo
Auflo
and 4.4.2 StAbE
Stabe
Press and hold 0/ESC and Start/Stop simultaneously until ALLGE appears in the display.
WAAGE
AuFLo Selection of display steps
StAbE Basic settings weighing elements (Number / Max Load / mV/V)
StAbA Number of connected weighing elements
LASt Maximum load of connected weighing elements (see type plate of
weighing element)
StAbS mV/V value of connected weighing elements (see type plate of
weighing element)
StAbE Adjustment completed
8.2 Input of time and date
Settings under 4.1.2
Time
Uhr
, 4.1.3 Date
dAt
and 4.1.4 Year
JAhr
ALLGE
Uhr Input of time
dAt Input of date
JAhr Input of year
8.3 Settings for printers or large-size displays
Settings under 4.2 Menu Interfaces (
Schnt)
Schnt
CON 1 Function of 1st serial interface
AuS Interface 1 deactivated
GAZ Output format for T.E.L.L. large-size display
druck Output format for T.E.L.L. printer, data logger or Telog software
GAJun Output format for T.E.L.L. large-size display (only for Jun 1, 2, 3, 4)
CON 2 Function of 2nd serial interface (optional)
AuS Interface 2 deactivated
GAZ Output format for T.E.L.L. large-size display
druck Output format for T.E.L.L. printer, data logger or Telog software
GAJun Output format for T.E.L.L. large-size display (only for Jun 1, 2, 3, 4)
bAud Entry of baud rate of serial interfaces (1 and 2)
PArIt Entry of parity of serial interfaces (1 and 2)
bIt L Entry of bit length of serial interfaces (1 and 2)

Table of Contents