-33-
Instructions for connection:
1. Connect the pump via laptop
a. Connect the pump and laptop using a standard or crossover Ethernet cable
b. Observe the RJ45 communication LED’s with both the pump and laptop powered
i. LED1 / LINK: Slowly ashing when powered, solid when link established
ii. LED2 / ACT: Flashing yellow when link established
c. Open any Web Browser
i. IMPORTANT: Connection to the Internet is NOT required
d. Enter the pumps IP Address or NetBIOS Name in the web browser
i. Default IP is 192.168.0.245
ii. Default IP for a Lag or Back-up pump in a parallel application
is typically 192.168.0.246
e. Once connected, the Pump Overview HTML pages include
i. Overview Tab: Displays the pumps real time operational data
ii. Pump Tab: Access to various pump setting adjustments and is where the minimum
Pump RPM setting is changed. See example below
iii. Network Tab: Ability to change the pump network connection
iv. Log Tab: Displays current and past error codes
v. More Tab: Used to update software and rmware