-42-
17.10 Binary Inputs (Object Type 3) • NOTE: Values are read-only
Instance Object Name Unit Description
BI.0 Remote Access Active
---
Indicates remote control
0 = Local
1 = Remote (Bus control).
BI.1 Near Minimum Speed --- Indicates if the pump is running near minimum speed.
0 = No
1 = Yes.
This ag is set when speed falls below 1/3 of rated maximum
BI.2 Near Maximum Speed --- Indicates if the pump is running near maximum speed.
0 = No
1 = Yes.
This ag is set when power or speed is over 95% of rated maximum.
17.11 Binary Outputs (Object Type 4)
Instance Object Name Unit Description
BO, 0 Remote Access Enable
---
Control bit that sets local or remote control.
Setting this bit will enable pump control over BACnet.
0 = Local
1 = Remote
BO, 1 Reset Faults --- Setting to 1 will try to clear any pending faults
(not needed as faults are auto cleared)
0 = No reset
1 = Trigger reset
BO, 2 Save Conguration --- Write analog outputs to non-volatile memory.
After next power cycle, pump will start with saved conguration.
0 = No reset
1 = Trigger save