PREMIER SX INSTALLATION MANUAL.
Approved Document No: GLT.MAN-101T
PAGE 16
Issue : 1.6s Authorised: GH Date: 06/11/2002
12. PANEL SPECIFICATIONS
12.1 ENCLOSURE SPECIFICATIONS
DESCRIPTION VALUE
ENCLOSURE SIZE 355 x 275 x 100 mm
TOP CABLE ENTRIES 12 x 19mm DIA GROMMETED ENTRIES
BOTTOM CABLE ENTRIES 2 x 19mm KNOCKOUT ENTRIES
REAR CABLE ENTRIES 2 SNAP OUTS, 60 x 20mm
12.2 ELECTRICAL SPECIFICATIONS
ELECTRICAL DESCRIPTION VALUE
MAINS VOLTAGE 230V AC +/- 10% @ 50/60 Hz
BATTERY VOLTAGE 24V DC (2 X 12V SLA BATTERY)
SYSTEM VOLTAGE 24V DC NOMINAL (18 32 V)
SYSTEM VOLTAGE RIPPLE 2V PK-PK MAX
CHARGER SIZE UP TO 7AH in 24 Hours
ZONE VOLTAGE 21V DC NOMINAL (20 - 22.5V)
SOUNDER ALARM OUTPUTS 2 x 400mA @ 24V DC (Nominal)
AUXILIARY FAULT OUTPUT 1 x RELAY SELV (1A MAX)
AUXILIARY FIRE OUTPUT 1 x RELAY SELV (1A MAX)
NUMBER OF ZONES 1/2/4/6/8
MAXIMUM ZONE CAPACITY 32 DEVICES PER ZONE
MAXIMUM ZONE RESISTANCE 80 ohms
REMOTE SOUNDER ACTIVATION VIA N/O CONTACTS
SOUNDER ACTIVATION DELAY 0-9 MINUTES -IN 1 MIN INCREMENTS
ZONE END OF LINE DEVICE DIODE (CATHODE STRIPE TO +)
SOUNDER END OF LINE DEVICE 10 K RESISTOR
CHARGER VOLTAGE 28.4V @ 25
o
C (NO BATTERY CONNECTED)
ZONE SHORT CIRCUIT PROTECTION 100mA
CHARGER SHORT CIRCUIT PROTECTION Batteries less than 20V
TOTAL CHARGER OUTPUT 1.1 Amp