AIR PURGING WITH VACUUM PUMP 
Please note this should be completed for each refrigerant 
circuit (each indoor unit) 
 
1.  Check that pipelines connection have been properly 
connected, remove the charging port cap, and connect the 
manifold gauge and the vacuum pump to the charging 
valve using service hoses as shown 
2.  Open the valve on the low-pressure side of the manifold 
gauge, then run the vacuum pump. Vacuum the indoor unit 
and the connecting pipes until the pressure in them lowers 
to below 1.5mmHG (The operation time for vacuuming is 
about 10 minutes). When the desired vacuum is reached, 
close the low pressure valve on the manifold and stop the 
vacuum pump. 
3.  Disconnect the service hoses and fit the cap to the 
charging valve. 
4.  Remove the blank caps, and fully opens the spindles of the 
2-way and 3-ways valves with a service valve wrench. 
5.  Tighten the blank caps of the 2-way and 3-ways valves, 
applying the torque listed in the table above. 
 
ADDING REFRIGERANT 
Refrigerant must be added if the pipe length is more than 5 metres (16'5"). This 
operation can only be performed by a professional F-Gas engineer, for the additional 
gas amount, see the below 
 
 
GAS LEAKAGE INSPECTION
 
After the pipeline connection is done, use a leakage inspection device to carefully check 
if there is any leakage at the joints. This is an important step to ensure the quality of 
installation.  Once a leak is detected, proper action should be taken immediately. 
 
INSTALL THE WATER DRAINAGE PIPE 
 
1.  For good drainage, the drain 
hose should be angled 
downwards. 
2.  Do not pull on or bend the drain 
hose or flood its end with water. 
3.  When the long drainage hose 
passes through indoor areas, it 
should be wrapped in insulation.