1-7
Example of connection between the 7200MA and typical peripheral devices are
shown as below.
Power supply
Power su
pp
l
y
Switch
(
NFB
)
Electroma
g
netic
A
C reactor
In
p
ut noise
filte
r
7200M
Zero phase core
Induction
motor
Install fast
action fuse
And earth
Leakage
breaker
contactor
inverte
r
Power supply switch(NFB) and earth leakage breaker
Choose the power supply switch(NFB) of proper current rating.
Do not use the power supply switch(NFB) as the switch that the
inverter is used to control the running or stop of motor.
When the earth leakage breaker installed to protect the leakage
current fault, be sure that the earth leakage breaker has the
sensitivity amperage200mA per inverter and operation time
0.1 sec to avoid false-triggering.
Electromagnetic contactor
In normal operation, you don’t need an electromagnetic
contactor. However, you need to install an electro-magnetic
contactor while in the case of sequence control through the
external device or automatically re-start after power outage.
Do not use the electromagnetic contactor as the switch that
control the operation of running or stop.
AC reactor
The AC-side reactor on the input AC side can improve the
power factor and suppress the surge current.
Install fast action fuse
To ensure the safety of peripheral devices, please install the fast
action fuse. Regarding the specification, please refer to P1-28.
Input noise filter
7200MA will comply with the EN55011 class A regulation if an
input noise filter (specified by TECO) is used.
Please refer to the selection guide “1.9 Peripheral device” on
page 1-23.
7200MA inverter
Input power supply can be connected to any terminal R/L1,
S/L2, T/L3 on the terminal block. The phase sequence of input
power supply is irrelevant to phase sequence.
Please connect the ground terminal E to the site ground
securely.
Zero phase core
Install the zero phase corer to eliminate noise transmitted
between the power line and the inverter.
Please refer to the selection guide “1.9 Peripheral device” on
page 1-25.
Induction Motor
If one inverter is to drive more than one motors, the inverters
rated current should be much greater than the sum of total
current of motors while in operation.
The inverter and the motor should connect to the ground
separately.