4-23
Group 01: V/F Control Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
01-00
V/F Curve
Selection
0~FF F - O O X X X X O *3
01-01 Reserved
01-02
Maximum Output
Frequency of
Motor 1
4.8~599.0
50.0/
60.0
Hz O O O O O O O *8
01-03
Maximum Output
Voltage of Motor
1
200V: 0.1~255.0 -
V O O X X X X O *8
400V: 0.2~510.0 -
575V: 0.1~670.0 -
690V: 0.1~804.0 -
01-04
Middle Output
Frequency 2 of
Motor 1
0.0~599.0 0.0 Hz O O X X X X O
01-05
Middle Output
Voltage 2 of
Motor 1
200V: 0.0~255.0
0.0 V O O X X X X O *8
400V: 0.0~510.0
575V: 0.0~670.0
690V: 0.0~804.0
01-06
Middle Output
Frequency 1 of
Motor 1
0.0~599.0 3.0 Hz O O X X X X O
01-07
Middle Output
Voltage 1 of
Motor 1
200V: 0.0~255.0
*
V O O X X X X O *8
400V: 0.0~510.0
575V: 0.0~670.0
690V: 0.0~804.0
01-08
Minimum Output
Frequency of
Motor 1
0.0~599.0
VF:1.5
Hz O O O O O O O
VF+PG:
1.5
SLV:
0.6
SV:0.1
PMSV:
0.1
PMSLV
:9.0
SLV2:
1.0
01-09
Minimum Output
Voltage of Motor
1
200V: 0.0~255.0 7.5
V O O X X X X O *8
400V: 0.0~510.0
15.0
575V: 0.0~670.0
690V: 0.0~804.0
01-10
Torque
Compensation
Gain
0.0~2.0 0.5 - O O X X X X O *1