1.10 MAINTENANCE
Scheduled routine maintenance includes inspections, checks, and interventions that systematically monitor
the condition of various parts to prevent interruptions and breakdowns. These operations must be carried out
by Qualified Personnel. Maintenance tasks should be performed in accordance with the times indicated in the
following table:
Component Frequency Operation
Appliance
Every month Check the tightening of the components.
Every year Check the integrity of electrical components and electrical cables
Every year Efficiency and safety checks
Every year Inspection of informative labels
Fan Every month Check the operation.
Capacitor Every month Visual inspection to check if it is clean or not.
Compressor Every month Check the mechanical operation.
Filter Every month Check and clean
Tab. 1-3
1.10.1 CLEANING
Cleaning the filter should be done at least once a month and as needed based on the level of dustiness in the
installation environment. Open the plastic grille (Ref. A6, Fig. 14) from the top and remove the filter (Ref. A5,
Fig. 14). Clean the filter by washing it with lukewarm water.
CAUTION: Do not use hard brushes or abrasive materials to avoid damaging the filter.
Reposition the filter (Ref. A5, Fig. 14) and close the plastic grille (Ref. A6, Fig. 14).
1.11 DIAGNOSTICS, ISSUES, CAUSES, AND REMEDIES
Below, we present a table that is useful for the operator to recognize the defects observed in the operation.
Repairs on the appliance will be carried out by a specialized and trained maintenance technician.
2. SPARE PARTS
To ensure satisfactory and consistent operation, it is necessary to use exclusively original parts and
accessories. The use of non-original spare parts is not recommended. In the event that this occurs, Teco S.r.l.
disclaims any responsibility for any damage to persons or property resulting from non-compliance with the
above instructions.
3. TABLE OF ISSUES, CAUSES, REMEDIES
Tab. 2-1
The display doesn’
turn on
Loss of electrical power.
Check that the plug is fully inserted into the power
outlet (Ref. A5, Fig. 4).
Poor water cooling.
Insufficient water flow.
Check the proper operation of the pump (not
supplied) (Ref. A1, Fig. 12-13).
Insufficient thermal insulation.
Provide insulation for the tank walls and pipes to
reduce thermal losses.
Air exiting from the ventilation
grille at room temperature.
Lack of refrigerant in the compressor, please
contact the local TECO S.r.l. dealer.