26
Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
07-00
Momentary
Power Loss/
Fault
Restart
Selection
0: Disable
0
1: Enable
07-01
Fault Auto-
Restart
Time
0~7200 0
07-02
Number of
Fault Auto-
Restart
Attempts
0~10 0
07-03 Reserved
07-04
Direct Start
at Power on
0: When the
external run
command is
enabled,
direct start at
power up
1
1: When the
external run
command is
enabled,
unable to
direct start at
power-up.
07-05
Automatic
start delay
at power up
1.0~300.0 3.5
07-06
DC Injection
Braking
Start
Frequency
0.0~10.0 0.5
07-07
DC Injection
Braking
Current
0~100 50
07-08
DC Injection
Braking
Time at
Stop
0.00~10.00 0.50
07-09
Stop Mode
Selection
0: Deceleration
to Stop
0
1: Coast to
Stop
2: DC Braking
Stop
3: Coast to
Stop with Timer
07-10
~
07-12
Reserved
07-13
Low Voltage
Detection
Level
200V:
150~300
190
400V:
300~600
380
07-14
Pre-
excitation
Time
0.00~10.00 2.00
07-15
Pre-
excitation
50~200 100 *6
Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Level
07-16
DC Injection
Braking
Time at
Start
0.00~100.00 0.00
07-17 Reserved
07-18
Minimum
Base block
Time
0.1~5.0 -
07-19
Direction-
Detection
Speed
Search
Operating
Current
0~100 50
07-20
Speed
Search
Operating
Current
0~100 20
07-21
Integral
Time of
Speed
Searching
0.1~10.0 2.0
07-22
Delay Time
of Speed
Searching
0.0~20.0 0.2
07-23
Voltage
Recovery
Time
0.1~5.0 2.0
07-24
Direction-
Detection
Speed
Search
Selection
0: Disable
1
1: Enable
07-25
Low voltage
Detection
Time
0.00~1.00 0.02
07-26
SLV Speed
Search
Function
0: Enable
0
1: Disable
07-27
Start
Selection
after Fault
during SLV
Mode
0: Speed
search start
0
1: Normal Start
07-28
Start
Selection
after
External
Base Block
0: Speed
search start
0
1: Normal Start
07-29
Run
Command
Available
during DC
Braking
0: Disable
(Run command
isn’t
available until
the DC braking
is completely
done)
0
Note1
1: Enable
07-30 Reserved
07-31 Reserved