EasyManua.ls Logo

TECO F510 series - Page 28

TECO F510 series
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
07-32
Speed
Search
Mode
Selection
0: Disable
1: Mode1:
Start a
Speed
Search at
Power on
2: Mode2:
Start Speed
Search
upon the
Motor Run
0
Note2
07-33
Start
Frequency
of Speed
Search
Selection
0: Maximum
Output
Frequency of
Motor
1: Frequency
Command
0
Note2
07-34
Start short-
circuit
Braking
Time
0.00~100.00 0
Note2
07-35
Stop Short-
circuit
Braking
Time
0.00~100.00 0.5
Note2
07-36
Short-circuit
Braking
Current
Limited
Level
0.0~200.0 100
Note2
07-42 Voltage limit
gain
0.0~50.0 0
Note3
07-43
Short-circuit
Braking
Time of PM
Speed
Search
0.00~100.00 0.00
Note4
07-44
DC Braking
Time of PM
Speed
Search
0.00~100.00 0.00
Note4
07-45
STP2
Function
Selection
0:STP2 Enable
0
Note6
1:STP2 Disable
07-47
PM Speed
Switching
Frequency
Mode
0: Disabled
0
Note9
1: Mode 1
2: Mode 2
Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
08-00
Stall
Prevention
Function
xxx0b: Stall
prevention is
enabled in
acceleration
0000b
xxx1b: Stall
prevention is
disabled in
Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
acceleration
xx0xb: Stall
prevention is
enabled in
deceleration
xx1xb: Stall
prevention is
disabled in
deceleration
x0xxb: Stall
prevention
is enabled
in operation
x1xxb: Stall
prevention
is disabled
in operation
0xxxb: Stall
prevention
in operation
decelerates
based on
deceleration
time 1
1xxxb: Stall
prevention
in operation
decelerates
based on
deceleration
time 2
08-01
Stall
Prevention
Level in
Acceleration
20~200 120
08-02
Stall
Prevention
Level in
Deceleratio
n
200V: 330~410 385
400V: 660~820 770
08-03
Stall
Prevention
Level in
Operation
30~200 120
08-04 Reserved
08-05
Selection for
Motor
Overload
Protection
(OL1)
x
xx0b: Motor
Overload
Protection is
disabled
0001b
xxx1b: Motor
Overload
Protection is
enabled
x
x0xb: Cold
Start of Motor
Overload
xx1xb: Hot
Start of Motor
Overload
x0xxb:

Other manuals for TECO F510 series