Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Standard Motor
x1xxb: Special
motor
0xxxb:
Reserved
1xxxb:
Reserved
08-06
Start-up
Mode of
Overload
Protection
Operation
(OL1)
0: Stop Output
after Overload
Protection
0
1: Continuous
Operation after
Overload
Protection.
08-07
Motor
Overload
(OL1)
Protection
Level
0: Motor
overload (OL1)
Protection 0
0
Note3
1: Motor
overload (OL1)
Protection 1
2: Motor
overload (OL1)
Protection 2
08-08
Automatic
Voltage
Regulation
(AVR)
0: Enable
0
1: Disable
08-09
Selection of
Input Phase
Loss
Protection
0: Disable
0
1: Enable
08-10
Selection of
Output
Phase Loss
Protection
0: Disable
0
1: Enable
08-11
08-12
Reserved
08-13
Selection of
Over-
Torque
Detection
0: Over-Torque
Detection is
Disabled.
0
1: Start to
Detect when
Reaching the
Set Frequency.
2: Start to
Detect when
the Operation
is Begun.
08-14
Selection of
Over-
Torque
Operation
0: Deceleration
to Stop when
Over-Torque is
Detected.
0
1: Display
Warning
when Over-
Torque is
Detected. Go
on Operation.
2: Coast to
Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Stop when
Over Torque
is Detected
08-15
Level of
Over-
Torque
Detection
0~300 150
08-16
Time of
Over-
Torque
Detection
0.0~10.0 0.1
08-17
Selection of
Low-Torque
Detection
0: Low-Torque
Detection is
Disabled.
0
1: Start to
Detect when
Reaching the
Set Frequency.
2: Start to
Detect when
the Operation
is Begun.
08-18
Selection of
Low-Torque
Operation
0: Deceleration
to Stop when
Low- Torque is
Detected.
0
1: Display
Warning when
Low- Torque is
Detected. Go
on Operation.
2: Coast to
Stop when
Low-Torque is
Detected
08-19
Level of
Low-Torque
Detection
0~300 30
08-20
Time of
Low-Torque
Detection
0.0~10.0 0.1
08-21
Limit of Stall
Prevention
in Acc over
Base Speed
1~100 50
08-22
Stall
Prevention
Detection
Time in
Operation
2~100 100
08-23
Ground
Fault (GF)
Selection
0: Disable
0
1: Enable
08-24
Operation
Selection of
External
Fault
0: Deceleration
to Stop
0
1: Coast to
Stop
2: Continuous
Operation